Start with the measurement or protection task
Define what each transformer must do before choosing a ratio. A metering CT may need to provide useful resolution across the expected operating range, while a protection CT must be considered against the relay function and fault conditions it is intended to support. A VT may serve metering, protective relaying, synchronizing, or more than one function. Identify every connected device and its purpose rather than treating all instrument transformers as interchangeable.
For a new switchboard assembly or a retrofit, document the system configuration and the point where measurements are taken. Confirm phase arrangement, grounding, nominal and maximum system conditions, expected load range, and the protection scheme. Ask whether the devices share a core or require separate cores, and whether the application needs phase, residual, or neutral-current measurement. These decisions affect transformer arrangement, device compatibility, and the wiring drawings needed for review.
Choose ratios for the system and connected devices
A CT ratio relates primary current to secondary current; a VT ratio relates primary voltage to secondary voltage. The selected ratio must suit both the electrical system and the input requirements of the meter or relay. Consider normal operating values as well as the range relevant to protection. A ratio chosen only from nominal load can leave a meter poorly matched to expected readings or fail to address the relay’s specified input and application requirements.
Provide the proposed primary and secondary values, device input ratings, and any device-specific ratio or scaling settings when requesting a configuration. Confirm whether the connected equipment accepts the intended secondary values and how it represents measured quantities. For retrofit work, record existing transformer nameplate data and verify that the replacement matches the actual circuit and devices; do not rely on an old drawing alone. Final ratios and suitability require project-specific engineering review.
Review accuracy and burden as a connected system
Burden is the electrical load placed on an instrument-transformer secondary by connected devices and interconnecting conductors. For CTs, the burden includes device inputs, lead resistance, terminal connections, and other loads on that circuit. VT circuits also have limits and application requirements that must be checked against the connected devices. The transformer’s accuracy and performance cannot be assessed independently of the complete secondary circuit.
List the meters, relays, transducers, and other devices connected to each core or secondary, including their documented input burden where available. Include approximate conductor material, route length, and wire size so lead effects can be evaluated. Confirm the required accuracy class or protection performance with the project designer and device documentation. Avoid assuming that an existing transformer’s capacity or accuracy will carry over when devices, cable routes, or protection functions change.
Specify polarity, phase relationship, and grounding
Polarity markings identify corresponding primary and secondary terminals and are essential to correct current direction, phase relationships, and protective functions. Incorrect polarity or phase assignment can produce misleading meter readings or interfere with differential, directional, residual, and other relay applications. The required terminal designations and phase mapping should be shown consistently on the one-line diagram, wiring diagrams, transformer schedule, and device connection information.
State the intended polarity convention and identify how each CT and VT connects to its associated phase and device terminal. Document the secondary grounding approach and any neutral or residual connections required by the design. For replacement components, compare existing markings and drawings with the actual application before specifying a match. Wiring and verification must be performed by qualified personnel using approved project procedures; this guide is not a field test or installation procedure.
Coordinate wiring, terminals, and retrofit interfaces
A sound transformer selection can still be unsuitable if its physical and wiring interfaces do not fit the assembly. Specify mounting arrangement, available space, primary connection method, secondary terminal style, conductor entry, clearances, and access requirements. For a new assembly, coordinate these details with the switchboard layout and control schematics. For a retrofit, provide enclosure and compartment information, connection dimensions, existing terminal details, and any constraints that affect installation.
Identify the secondary circuits and terminal points for every meter or relay, including test switches or shorting provisions where required by the design. Confirm that drawings distinguish CT circuits from VT circuits and show protective devices, grounding, fusing, and terminal references as applicable. Do not assume a component is a direct replacement because its ratio appears identical: dimensions, insulation requirements, connections, and device compatibility also matter. Installation, servicing, testing, and energization require qualified personnel following approved procedures.
Prepare a complete specification and quotation package
A useful request for pricing includes the application, system data, transformer type and quantity, proposed ratios, required accuracy or protection performance, and the devices each transformer will serve. Include one-line and control drawings, transformer schedules, device manuals or input data, and retrofit photographs or dimensions when relevant. Identify project standards and required submittals. Clear documents help us review the requested configuration and identify questions before a new assembly or new retrofit components are quoted.
Ask for confirmation of the proposed configuration, applicable standards, drawing scope, component origin, test documentation, availability, and project-specific lead time as part of quotation review. UL 891 applies to switchboards; it should not be treated as a blanket listing for every instrument transformer or configuration. Listing and applicable standards must be verified for the specific assembly. Customers may specify American components, but domestic-content requirements and component origin should be addressed and confirmed for each quotation rather than assumed.