400-Amp Switchgear

400-Amp Low-Voltage Switchgear

We manufacture new 400-amp low-voltage switchgear to project specifications for customers across Texas and ship nationwide from the United States. At this rating, the main design questions extend beyond ampacity: the power circuit breaker arrangement, bus configuration, feeder count and type, and available fault current all shape the assembly. We review these requirements with the project team before preparing a quotation; equipment configuration, component origin, lead time, and applicable documentation are confirmed for each project.

UL 891 switchboardsMADE IN USAFAST lead times
NEW EQUIPMENT. PROJECT FOCUSED.SERVING TEXAS
Electrical equipment secured for shipment

NEW SWITCHGEAR FOR YOUR PROJECT

MANUFACTURING / EQUIPMENT / TEXAS

Choose the Main Power Circuit Breaker Arrangement

A 400-amp assembly may be scoped around a main power circuit breaker and a set of outgoing feeder devices, but the one-line diagram determines how those devices should be arranged. Clarify whether the main is incoming from a transformer, generator, or another source, and whether the design calls for a single main, multiple sources, or a transfer arrangement. Identify any required tie breaker and describe normal and alternate operating states.

For the main breaker, provide the required frame and trip characteristics if established by the engineer, along with the intended trip functions and control needs. State whether metering, ground-fault protection, shunt trip, undervoltage release, or auxiliary contacts are required. These are configuration decisions, not assumed inclusions. We use the project requirements to assess a proposed arrangement and identify information that remains open before pricing.

Define Bus Construction and System Interfaces

The 400-amp rating does not, by itself, define the complete bus design. Specify the system voltage, phase and wire arrangement, grounding method, and whether the assembly will use a common bus or separate sections. Note the intended incoming cable or busway interface, entry direction, termination space, and any constraints on enclosure dimensions or access. These details affect how the switchgear fits the electrical room and connects to adjacent equipment.

If the project requires a particular bus material, plating, insulation, separation, or ground-bus arrangement, state that in the specification and drawing package. Also identify whether neutral conductors need a full-size or otherwise engineered arrangement based on the connected loads and design. We review the requested bus details as part of the configuration; the final design must account for the project’s electrical requirements and applicable standards.

Plan Feeder Count, Device Types, and Space

List each outgoing feeder by load served, required rating, conductor or cable termination needs, and preferred protective-device type. The feeder schedule helps determine whether the lineup should use molded-case circuit breakers, power circuit breakers, or a combination where the design allows. Include spare or future feeder positions separately from active circuits, and distinguish installed devices from provisions for later additions.

Review physical and operational needs for every feeder: cable entry direction, lug or termination requirements, access for maintenance, metering or monitoring, and any interlocking or remote-control functions. A high feeder count may affect section layout and usable wiring space, while large conductors can drive termination requirements. Provide enclosure and room constraints early so the proposed lineup can be evaluated against the installation plan rather than only the one-line.

Establish Available Fault Current and Interrupting Needs

Provide the calculated available fault current at the switchgear line terminals, the calculation basis, and the system conditions used. Useful inputs include transformer impedance and rating, upstream protective-device information, conductor lengths and sizes, and any utility or generator contribution included in the study. Identify whether multiple sources can operate in parallel, since source combinations may change the fault-current duty seen by the assembly.

The fault-current value is essential to evaluating breaker interrupting capability and the assembly’s short-circuit withstand requirements. Do not treat the 400-amp continuous-current designation as evidence that a particular fault-duty rating is suitable. If the short-circuit study is preliminary or unavailable, flag that status in the inquiry. The final configuration and applicable ratings must be confirmed against the project study and equipment documentation.

Coordinate Protection Across Main and Feeder Devices

Protection coordination depends on more than selecting breakers by amp rating. Share the current coordination study or its design criteria, including upstream and downstream protective devices, expected load characteristics, and any required clearing-time objectives. Identify critical loads, motor starting or transformer inrush concerns, and whether selective coordination is required by the project documents or applicable code.

Ask the engineer to identify the preferred trip functions, settings range, and coordination approach for the main and each feeder. Where settings are not yet finalized, provide the study assumptions and note who will establish and approve final settings. We can evaluate the requested device arrangement against the supplied project information, but coordination must be verified by the responsible design professional using the final system data.

Prepare a Complete 400-Amp Project Package

For a useful quotation, submit the one-line diagram, panel or feeder schedule, system voltage and grounding details, available-fault-current calculation, coordination study or criteria, and equipment-room or interface drawings when available. State the required drawing submittals, project schedule constraints, shipping destination, and any specified enclosure or environmental conditions. Identify requested American components explicitly; component origin and availability are confirmed during quotation review and are not a certification of domestic-content compliance.

We supply new equipment and new retrofit components only. If this is a replacement or modernization, describe the existing lineup, connection points, dimensions, and components to be replaced, and provide clear drawings or field-verified measurements. Compatibility and scope must be reviewed before a retrofit quotation. Listing and applicable standards should be verified for the specific configuration; UL 891 applies to switchboards and should not be treated as a blanket listing for every switchgear assembly.

LET'S BUILD SOMETHING

Start with
the details.

Tell us what you’re working on. The more you can share about your project, the better we can begin the conversation.